With the COVID-19 epidemic, the demand for mobile simple screening stations has greatly increased. There are relatively few cases of using container space as screening stations and setting them as positive pressure spaces, and the design reference benchmarks for such spaces are even rarer. This study uses simple ventilation equipment to verify the positive pressure effect of the 20-ft container space, and hopes to provide a reference for the design of related ventilation equipment systems in the future. The results show that when the frequency conversion simple fan is used to achieve indoor 2.0Pa, if there is no grille, the design ventilation frequency should be at least 6 times/h, and with the grille, the ventilation frequency should be at least 10 times/h. For general space use, the minimum ventilation rate must be met, and the design ventilation frequency of the fan should be at least 6 times/h, but the efficiency will slow down after 10 times/h. That is to say, when a simple ventilation device is used in the 20-ft container space, the fan is designed to ventilate at least 6 times/h. |