The research utilizes DOE-2 to analyze the central air-conditioning energy enduse of office building. The research makes use of several handy building envelope design variables as well as HVAC design variables onto the prediction model. These selected variables are able to effectively reflect on the annual AC energy consumption and can be fed back to the design for further renovating and provides the designer a better understanding on the interactions linking between the design variables and the energy consumption. The annual AC energy consumption is nowadays regulated by the ENVLOAD index from the Building Technical Code and the HVAC energy conservation calculation from Green Building Evaluation System in Taiwan. For the reasons to simplify and to increase the applicability, this paper utilized the variables that come from the above two calculation process to develop easy-to-use prediction models of annual AC energy consumption. The research analysis through the equivalent full load hours of the two major type chiller plants to establish the predicting models. The models come in three climate zones with two chiller types, all the R2s lie between 0.937 and 0.964. Furthermore, other HVAC equipment’s energy prediction model, such as HVAC pumps, AHU fans and cooling towers are also established. The coefficients of correlation lie between 0.995 and 0.999. |