英文摘要 |
There are lots of building components damaged by the extreme weather conditions, such as the typhoon, in Taiwan area every year. This situation will be a problem of safety of civilization lives. A suitable design criteria of wind loadings to these buildings is necessary for the designers and officers of buildings management. In this study couples of design codes and literatures are compared as the bases for the local provisions of design wind loads on buildings components and temple structures. Also a series of aerodynamics experiments about cylindrical tanks on buildings top were conducted to make up the necessary data. In experiments, the gap under the bottom of model and floor of wind tunnel was controlled as an important factor. The experimental results shown, that the gap will affect the wind force coefficients of models. But the design data provided by the code still can cover this variation. For the over turning moments of tank with different gap under the model were studied with the concept of equivalent loadings. The results shown, that the increasing of the gap under the tank will cause the equivalent loadings at the top of tank to be increased dramatically. This situation may cause the buckling of support columns under the tank and should be aware for the designer. The results also shown for the horizontal tank the change of attack angle of approaching flow, will change the project shape of tank into anti-symmetric. The generalized force of wind loadings will be increased. |