英文摘要 |
According to the past Building Technical Regulations in Taiwan, the old-fashioned hotels are legal building in public security check. However, proprietor usually ignores or the old-building style limited, unimproved for the fire egress facility and fire protection equipment, increasing damage of risks for this type's buildings. The passengers from other place are unfamiliar with the hotel environment. Therefore, the occupant casualties are serious in the hotel building fire. This study using the latest version FDS 5.5+ Evac 2.2computer program to reconstruct the fire numerical models of fire accident at a Bai-Syue Hotel in Taiwan. The computational results demonstrated good prediction of fire impact parameters (temperature various, heavy smoke movement and CO concentration) and occupants unimpeded egress time by comparing fire scene forensic reports.According to the computer simulation results in the fire flames continuing and the fire smokes spreading shows the smoke layer height moved down to 1.8 meters above the ground in the 2nd floor and the 3th floor approximately 245 seconds after the fire started. At this point during the fire, the people would be very difficult to escape from fire site. For this reason, the three persons died at around 639 seconds after the fire started. |