Taiwan is during an aged society to a super-aged society. While the elderly and disable population continues rising, more than 500 million people have urgent needs with elevators but live without elevators. And cause inconvenience to their daily life. In order to solve this problem, in 2011, the construction and planning agent ministry of the interior relax some regulations on addition of elevators in apartments with 5 and below 5 stories. And local governments also provide subsidy to encourage the addition elevators. However, limited by the exit width of the refuge floor, the realized cases of addition elevators are still rare. Based on this situation, this thesis uses Verification Guideline of Buildings Evacuation Safety Performance-based Design for static evaluations and derivate the impact factors of total evacuation time in apartments with 5 and below 5 stories. And also conduct dynamic simulations with PATHFINDER. As a result, fix the number of people in apartments with 5 and below 5 stories, there is no significant effect with total evacuation time when reduce the exit width from 120cm to 75cm. This result can be the key according for the construction and planning agent ministry of the interior amend article 55 of Building Technical Regulations to relax exit width of refuge floor. And promote the addition elevators in apartments with 5 and below 5 stories.