The electronic equipment would be damaged by the corrosive gas in outdoor and indoor environment. In this study, different prevention method was evaluated in two different field cases, respectively in sulfur geothermal region and metropolitan region polluted by the hydrogen sulfide (H2S). These corrosion prevention methods include the control of humidity and the application of the vapor phase corrosion inhibitor (VPI). Before the field testing, laboratory research were conducted to achieve the best prevention effect for the field application. These major laboratory researches include a flowing mixed-gas test, the humidity-controlling of cabinet and the thin-electrolyte- layer electrochemical technique. The results indicated that the humidity lower than 60 % can significantly decrease the H2S attack. Meanwhile, VPI will suggest more effective prevention from H2S-induced corrosion than the humidity-controlling method. In addition, it will be helpful for choosing the VPI by the electrochemical impedance measurements in the thin-electrolyte- layer. |