| 英文摘要 |
Taiwan islands locate in sub-tropic area. In this climate condition, the insulators on transmission and distribution lines along the seashore suffer from the impact of sea-wind, salt-fog and industrial pollutants respectively. Comparing to other climates, the severe weather parameters are significantly influence in insulator performance. Contamination flashovers have become the greatest concern to power lines during the past decades. A number of power failures are recorded on electric networks. To solve this problem, so far various efforts , gradually replacement of conventional insulators by polymer insulators for specific area have been made. In other words, polymer insulators serve as a countermeasure against contamination problems. This project is initiated in distribution lines aiming to investigate HDPE polymer insulators failure events and establish the fracture analysis techniques, in the consequence of improving power quality in distribution lines. The main results in this project are acquiring polymer insulators application information both in domestic and overseas, establishing analysis techniques both in materials (FTRI/TGA/DSC/SEM) and electricity (UV Corona Image Monitoring) and referring maintenance criteria on polymer insulators service. The failure occurred in the vicinity of the bottom of insulators with accumulated contaminants which caused tracking and erosion phenomena and induced high-temperature damage. |