| 英文摘要 |
Leakage occurred from a 12-inch gas pipeline in Hsinchu Region. A thumb size of localized corrosion was found after inspections. The outlook of the corrosion position is smooth and shining. According to original designs, the pipeline has coating wrap and cathodic protection system. However, leakage from corrosion still took place. Hence, some blind spots or unknown reasons exist during maintenance stage. To understand the damaged reasons, close internal survey, coating wrap inspections, and cathodic protection system evaluation were performed to investigate stray current interference. The present paper includes ( 1 ) analyses of damaged reasons, ( 2 ) improvements of anti-corrosion system, and ( 3 ) a comparison before and after improvements. |