英文摘要 |
This study aimed to inspect the electric hazards in the laboratories etc. of a Institute. We formed the basis of theory by means of analyzing document and deduced the check-list of electric hazards. Then, we inspected the field by related electrical instruments. In electrical safety management, we found the following faults: l.the labor safety & health staff wasn't hired, 2.the self-inspection plan wasn't made and carried out, 3.labor safety & health items weren't done when consigning a contract, 4.1abor education & training of safety & health weren't enforced, 5.the Act & related safety & health regulations weren't disseminated, 6. safety & health working rules weren't set, 7.the electrical technician wasn't hired, 8.the workers' complaints weren't accounted. In the facility, we found 4 faults: 1.the insulation resistance didn't meet the Act & related safety & health regulations, 2.the grounded conductors weren't settled, 3.the exposed charges weren't protected, 4. the interim wires were put on the roads. In the end, we offered our suggestions to improve the above faults. |