英文摘要 |
Combustible wood cribs with fixed fire load (5kg/m2 ) are heated by a fix fire source (25kW-200s) in ISO 9705 room is used to investigate effect of the density and the distributions of the combustible on the fire sustaining time. L9(34 ) orthogonal table from Taguchi method is used arranging experiment parameters, i.e. wood crib packing density and the distribution. The distribution mode of fire sustaining time and its standard deviation are discussed statistically and are compared with the calculated one. The reliability region of calculated fire sustaining time is found to be +2σ . Statistics from experimental results shows that the experimental fire sustaining time is still about 0.4σ probability longer than the calculate one. Besides, from the results of wood crib burning, we found that at a fixed fire-load the fire growth rate and maximum heat release rate are inverse proportional to the density of the combustible. By using the t2 fire assumption on the growth rate of the wood crib, we found the fire growth rate is less correlated with the density of wood crib, but closely related to the distribution of wood crib. |