英文摘要 |
Summarized to ascertain stainless steel pipe dissolution in water in the iron (Fe) and the high value of clean water and drinking places for the water supply of iron (Fe) multiple of ratio 32 rate - ∞ rate, mainly resulting from the pipeline wall corrosion nodulation water supply system and news media reports about the pipeline more than five years to produce fouling and biofilm attached coincide. It is proposed pipeline water supply system made of stainless steel pipe of internal cleaning should be cleaned once every five years is appropriate. Summarized to ascertain Galvanized steel pipe dissolution in water in the iron (Fe) and the high value of clean water and drinking places for the water supply of iron (Fe) multiple of ratio 60 rate - 748 rate, Mainly due to corrosion resulting from the pipeline wall nodules, and galvanized steel pipe (GIP) is only ten years after the use of the line plug appears red rust water hazards. To ensure that galvanized steel pipe stainless steel tube is not updated as before, to continue to be used, and the plugs to ensure no rust red water phenomenon, it is recommended that water supply system pipe made of galvanized steel pipe of internal cleaning should be cleaned once per year appropriate. |